A single 0.5 µm particle can ruin a wafer, contaminate a sterile product or shorten the shelf life of a food product. For this reason, many industries make their most sensitive products in a cleanroom. In these spaces, the air distribution system becomes one of the main tools HVAC engineers have to keep particle concentration within the limits of the target class.

Fikret Sahin, Vice President & Director of Sales, MENA, Africa, India & Asia at FabricAir

Fikret Sahin

Vice President & Director of Sales, MENA, Africa, India, & Asia

Those limits, however, vary widely from one industry to another. A lab that tests food samples and a sterile filling line follow very different rules. Understanding these differences therefore helps engineers decide where fabric ducts for cleanrooms add the most value, and the starting point is the definition of a cleanroom itself.

What Is a Cleanroom?

In technical terms, a cleanroom is a room in which the concentration of airborne particles is controlled and classified. It is designed, built, and operated to control the introduction, generation, and retention of airborne particles.

These particles come from several sources: people, equipment and processes, materials and surfaces, and the supply air itself. To keep them under control, a cleanroom relies on three main mechanisms. First, high-efficiency filtration, typically using HEPA filters, helps remove particles from the supply air. Second, a controlled airflow pattern dilutes or sweeps away the particles generated inside the room. Third, a controlled pressure differential between adjacent areas helps maintain the intended airflow direction and limit the ingress of contamination. In addition, facilities often keep temperature and humidity within tight limits.

Even with all these mechanisms in place, cleanliness still depends on the occupancy state. People, equipment and processes all release particles, so a room that is very clean when empty will carry a higher particle load once work begins. ISO 14644-1 therefore defines three occupancy states, as-built, at-rest and operational, and a cleanroom’s class is always specified for a particular state. A room may, for example, be required to meet ISO Class 5 at rest but only ISO Class 7 in operation. Classifying each state against the same particle-concentration limits gives engineers a common reference for measuring performance.

Cleanroom Classes: ISO 14644-1 and GMP Grades

ISO 14644-1 is the main international standard for cleanrooms. It defines nine classes based on the maximum particle concentration per cubic meter of air, calculated with the formula Cn = 10^N × (0.1/D)^2.08. In this formula, N is the ISO class number and D is the particle size in micrometers.

For a given particle size, the permitted concentration generally increases by a factor of 10 for each step toward a less stringent ISO class. For ISO Class 5 at 0.5 µm, for example, the formula gives 10^5 × (0.1/0.5)^2.08, or about 3,520 particles/m³. At the ends of the scale, ISO Class 1 is the cleanest, while ISO Class 9 is the least stringent ISO classification and represents a relatively low level of airborne particle concentration compared with the other ISO cleanroom classes. Ordinary rooms should not be assumed to meet ISO 9 without measurement. For a given particle size, the permitted concentration generally increases by a factor of 10 for each step toward a less stringent ISO class.

Alongside ISO, many facilities still use the older US standard FED-STD-209E. Although it was withdrawn in 2001, terms such as “Class 100” or “Class 100,000” remain common. The table below shows the limits at 0.5 µm and how the two systems compare.

ISO 14644-1 class Max. particles ≥0.5 µm per m³ Nearest FED-STD-209E class
ISO Class 3 35 Class 1
ISO Class 4 352 Class 10
ISO Class 5 3,520 Class 100
ISO Class 6 35,200 Class 1,000
ISO Class 7 352,000 Class 10,000
ISO Class 8 3,520,000 Class 100,000
ISO Class 9 35,200,000 Roughly ordinary room air

The standard sets these particle limits, but it does not prescribe air change rates. Instead, the required airflow is a design decision based on internal particle generation, room volume and recovery time. In other words, each project defines its own airflow, and some sectors add further requirements on top.

Pharmaceutical manufacturing is the clearest example of this additional layer. In Europe, EU GMP Annex 1 divides cleanrooms for sterile products into Grades A to D. The grades set airborne particle limits and, depending on the grade and occupancy state, additional microbiological and process-control requirements. Grade A has defined limits for both at-rest and in-operation conditions, while requirements for lower grades are established according to the applicable process and contamination control strategy. Their relationship with ISO 14644 classes should therefore be treated as a correspondence, not as identical classification systems.

Annex 1 also gives two key guidance values for HVAC design. For Grade A unidirectional airflow systems, it gives 0.36 to 0.54 m/s at the working position. Between adjacent rooms of different grades, it gives 10 Pa as a guidance value for the pressure difference. In many less critical clean areas, non-unidirectional airflow is used to dilute and remove contaminants. This is also an airflow approach in which fabric air dispersion systems can be particularly effective, because the system can distribute filtered air evenly across the room

Why Fabric Air Dispersion Systems Suit Cleanrooms and Controlled Environments

Fabric ducts for cleanrooms are particularly well suited to non-unidirectional airflow, which is common in ISO 7 and ISO 8 environments. The same applies to many controlled environments in food, electronics and laboratories. In these rooms, fabric air dispersion systems offer several technical advantages over conventional systems:

  • Certified fabrics. FabricAir’s Combi fabrics (Combi and Combi ECO 20, 30, 60, 65, 70, 80, 85 and 90) hold an EN ISO 14644-1 certificate for cleanliness Class 3. The certificate confirms that these fabrics are suitable for air lines in cleanrooms and associated controlled environments. This is essential, since any component the supply air passes through after filtration must not add particles. The fabric alone, however, does not set the class of a room. Instead, the final class depends on the whole system, including filtration, airflow pattern, air change rate, pressure cascade and occupancy.
  • Low velocity in the occupied zone. Fabric ducts disperse air along their full length, either through the fabric itself or through flow models such as orifices, nozzles or micro-perforations. With micro-perforations, the air leaves each hole as a small, fast jet. Depending on the static pressure for the system, it can be as fast as or faster than the air inside the duct. Because each jet is so small, it mixes with the room air and slows down within a short distance of the duct. In one FabricAir installation using the MicroFlow model, air velocity inside the duct was 5.75 m/s, while the velocity measured 0,18 m from the duct was approximately 0.2 m/s. Low velocities in the occupied zone help minimize drafts and air movement near work surfaces/stations, which is beneficial where particle disturbance is a concern. To achieve the right pattern, engineers select the flow model according to room height, air volume and the required throw.
  • Reduced condensation risk. On a metal duct carrying chilled air, the outer surface can drop below the dew point of the room air. Permeable fabrics, in contrast, let a small amount of air pass through the entire duct surface. This helps keep the outer surface closer to room conditions and can reduce the risk of surface condensation, which could otherwise support microbial growth.
  • Antimicrobial protection. Where microbial growth on the duct material is a concern, selected fabrics can provide antimicrobial properties. Combi 80 and 90 and Combi ECO 80 and 90 have antimicrobial test reports according to AATCC and EN ISO 20645. In a fish processing facility in Sydney, for example, Combi 80 inhibits microbial growth on both the inner and outer surfaces of the ducts.
  • Antistatic options. Electronics production, in turn, needs protection against electrostatic discharge. Combi ECO 80 and Combi ECO 90 address this need, as both have been tested according to EN 1149-1, which assesses the electrical properties of materials relevant to electrostatic charge control.
  • Easy cleaning. Conventional systems can require specialist cleaning and significant downtime. Fabric ducts, on the other hand, can be taken down, washed and reinstalled, which can simplify cleaning and maintenance. To keep the room running, some facilities even keep a second set of ducts to install while the first one is in the laundry. Color can support this routine as well: on a white duct, dust and stains are easy to see, so staff can quickly spot when it needs washing.

These benefits have already been proven in practice. At NovaMed’s pharmaceutical facility in Turkey, white fabric ducts were used as part of the air distribution system in a facility designed to meet the Class 100,000 cleanroom standard., white fabric ducts were used as part of the air distribution system in a facility designed to meet the Class 100,000 cleanroom standard.

White is a common choice in cleanrooms and laboratories, yet no single international rule sets the color of air ducts. ISO 14644-1 does not prescribe a specific duct color. Color selection is generally driven by project requirements, hygiene procedures, visibility of contamination, aesthetics and other applicable regulations. Food hygiene rules take a similar approach. EU Regulation 852/2004, for instance, requires ceilings and overhead fixtures to prevent the build-up of dirt, and some local authority guidance goes one step further by recommending light colors for walls and ceilings in food rooms.

In practice, the client usually chooses the color based on internal hygiene procedures and the look of the space. FabricAir fabrics come in a wide range of colors. In a Barcelona assembly hall, for example, Wallbox chose green Combi 70, one of the cleanroom-certified fabrics. Sterile production, however, sets much stricter conditions for anything installed in the room.

There, EU GMP Annex 1 states that pipes, ducts and other utilities should not be present in cleanrooms. Where they are unavoidable, they must be installed without recesses, unsealed openings or surfaces that are hard to clean.

Each project should therefore be assessed against its own contamination control strategy, together with the facility’s quality team.

To start that assessment, request a free consultation. Our experts will help you choose the right fabric, flow model and color for your cleanroom or controlled environment.

FAQs

ISO 14644-1 classes rate air cleanliness by particle concentration, from Class 1 to Class 9. GMP grades A to D come from EU GMP Annex 1 and apply to sterile pharmaceutical production. They add microbial limits and set requirements for both the at-rest and in-operation states.

Related terms: ISO 14644-1, EU GMP Annex 1, occupancy states

It is a term from the withdrawn US standard FED-STD-209E. Today, it corresponds roughly to ISO Class 8, which allows up to 3,520,000 particles of 0.5 µm or larger per cubic meter.

Related terms: FED-STD-209E, ISO Class 8, particle concentration

No. The certificate confirms that the fabric is suitable for air lines in cleanrooms up to that level. The class of the room depends on the whole system, including filtration, airflow pattern, airflow rate, pressure cascade and occupancy.

Related terms: EN ISO 14644-1 certificate, Combi fabrics, controlled environments

Yes. At a pharmaceutical facility in Turkey, white fabric ducts have helped the company comply with the Class 100,000 standard. For sterile production areas, EU GMP Annex 1 restricts ducts inside cleanrooms, so each project should be assessed with the facility’s quality team.

Related terms: pharmacy and labs, GMP compliance, sterile production

The ducts are removed, washed and reinstalled, which can simplify cleaning compared with conventional rigid ductwork. To avoid downtime, some facilities keep a second set of ducts to install during washing.

Related terms: washable ducts, hygiene, maintenance

No standard requires a specific color. ISO 14644 and EU GMP set requirements for particle levels, cleanability and non-shedding materials, so the client can choose the color. Many still prefer white, because it shows dust and stains clearly.

Related terms: duct color, hygiene inspection, cleanroom-certified fabrics